Airflow

Air changes per hour

The number of times per hour a room's volume of air is supplied or removed, calculated as airflow in cubic feet per minute times 60 divided by room volume in cubic feet. Cleanroom, pharmacy, and isolation room documents use it as a minimum ventilation or filtration rate.

Also called ACH, ACPH, air change rate

Direct answer

What does air changes per hour mean?

Air changes per hour is airflow expressed against room size: cfm × 60 ÷ room volume in cubic feet. A 1,512 cubic foot room supplied with 756 cfm receives 30 air changes per hour, the minimum USP 797 sets for an ISO 7 compounding room.

Air changes per hour: how it works

An air change rate turns airflow into a measure of how quickly a room's air is replaced, so rooms of different sizes can be held to one rule. In a well-mixed room, the concentration of anything released falls by about 63 percent with each air change, so the rate sets how fast the room dilutes what is released in it and how quickly it recovers after a disturbance.

Where you meet the term

  • In USP 797, which requires at least 30 air changes per hour in ISO 7 rooms and at least 20 in ISO 8 rooms.
  • In the CDC guidelines for airborne infection isolation rooms, which list at least 12 air changes per hour.
  • In a certification report, where measured airflow at each filter is added up and converted to a rate for the room.

How to check it

  1. Calculate the rate from design airflow. Multiply the room's supply airflow in cfm by 60 and divide by the room volume in cubic feet, measured to the room's finished ceiling. Owner check
  2. Measure airflow at every supply terminal. A certifier or balancer measures each terminal with a capture hood or velocity traverse, adds the results, and converts the total to air changes per hour. Technician

Figures you will see

Published air changes per hour figures with the condition each one applies to. Confirm against the documentation for your own model before acting on any of them.
ConditionFigureWhat it tells you
USP 797 ISO 7 roomAt least 30 ACPHRead against the model documentation
USP 797 ISO 8 roomAt least 20 ACPHRead against the model documentation
CDC airborne infection isolation roomAt least 12 ACH, 2 of them outdoor airRead against the model documentation
USP 800 hazardous drug storage roomAt least 12 ACPHRead against the model documentation
Read this twice

Air changes per hour: what it is not

  • Air changes per hour is not a measure of cleanliness. Two rooms at the same rate hold different particle counts when they release different amounts.
  • A high air change rate does not fix poor air distribution. Supply and return placement decide whether air sweeps the room or short-circuits past the work.

Air changes per hour questions

Does room volume include the space above the ceiling?

No. Air changes per hour uses the volume of the room the air serves, measured to the finished ceiling. The plenum above a cleanroom ceiling is part of the air path, not part of the room being ventilated.

Are air changes counted on supply or exhaust?

The governing document decides. A positive room is judged on its filtered supply, and in a negative room exhaust runs above supply by the offset, so designing supply to the required rate satisfies either reading.

How long does one air change take?

At 30 air changes per hour one air change takes two minutes, and at 12 it takes five. In a well-mixed room a 100 to 1 reduction of anything released takes about 4.6 air changes.

Where this definition comes from

Written from standards body publication, government guidance material held in the HVAC Bench evidence record. Where a document limits a definition to certain models, that limit is repeated here rather than generalised across a brand.

  • General Chapter 797, Pharmaceutical Compounding, Sterile PreparationsUnited States Pharmacopeia · standards body publication2023 revision, official 1 November 2023, for sterile compounding: at least 30 air changes per hour of HEPA-filtered supply in ISO 7 buffer rooms and anterooms and at least 20 in ISO 8 rooms, with at least 15 of them supplied by the HVAC system through HEPA filters; a minimum positive pressure differential of 0.020 inches of water column between the buffer room and anteroom and between the anteroom and unclassified space, monitored continuously; rooms maintained at 20 degrees Celsius or cooler and 60 percent relative humidity or below; and certification of primary and secondary engineering controls every six months.
  • Guidelines for Environmental Infection Control in Health-Care Facilities, Appendix B: AirCenters for Disease Control and Prevention · government guidanceCDC table of ventilation parameters: airborne infection isolation rooms with at least 12 total and 2 outdoor air changes per hour, air movement into the room, a pressure differential of at least 0.01 inches of water gauge (2.5 pascals), and all air exhausted directly outdoors unless recirculated within the room through HEPA filters; protective environment rooms with at least 12 air changes per hour, positive air movement, and HEPA filters of 99.97 percent efficiency at 0.3 micrometers.
  • General Chapter 800, Hazardous Drugs, Handling in Healthcare SettingsUnited States Pharmacopeia · standards body publicationEngineering controls for hazardous drugs: storage rooms and nonsterile containment secondary engineering controls externally vented, at least 12 air changes per hour, and negative between 0.01 and 0.03 inches of water column relative to adjacent areas; sterile hazardous drug buffer rooms of ISO 7 air quality with HEPA-filtered supply, externally vented, at least 30 air changes per hour, and negative between 0.01 and 0.03 inches of water column; an ISO 7 anteroom with at least 30 air changes per hour and at least 0.02 inches of water column positive to adjacent unclassified areas; and a containment segregated compounding area externally vented with at least 12 air changes per hour at the same negative pressure range.
  • ISO 14644-3:2019, Cleanrooms and associated controlled environments, Part 3: Test methodsInternational Organization for Standardization, via ANSI · standards body publicationTest methods for cleanroom performance: air pressure difference, airflow volume and velocity, airflow direction and visualization, recovery time using the 100 to 1 ratio with a 10 to 1 ratio added in the 2019 edition for less clean rooms, installed filter system leakage, containment leakage, temperature, and humidity. Recovery testing is optional and its acceptance is agreed between customer and supplier.