engineering

How to calculate a heat pump balance point

Find the outdoor temperature where heat pump output meets building heat loss, using a load line, capacity at temperature, and a worked crossing.

Editorial reviewBy Mukarram Haroon
Direct answer

What this means

The balance point is the outdoor temperature at which heat pump output equals the building heat loss. Find it by drawing the building load line from its zero-load temperature to its design load, drawing capacity from the manufacturer's performance data at the same temperatures, and reading the temperature where the two cross.

Equipment and model context

  • Air source heat pumps selected against a calculated building heat loss
  • Worked figures below are an example, not a published rating for any product

This is the design calculation and its arithmetic. It does not produce a number for a specific house or a specific product. The load must come from a room-by-room heat loss calculation and the capacity from the performance table for the exact model and airflow, at the design conditions for the site.

What this covers

  • Why the building load line starts at a temperature well below room temperature rather than at the origin.
  • How to read heating capacity at an outdoor temperature instead of taking the nominal rating.
  • The arithmetic that turns two lines into a single crossing temperature.
  • How the balance point sets the supplemental heat capacity a design has to provide.

What changes the result

  • The zero-load temperature moves with internal gains and solar gain, and shifting it moves the whole load line and the crossing with it.
  • Capacity data taken at maximum compressor speed overstates what the unit holds at a thermostat call it can satisfy at part load.
  • Defrost operation removes heating output during the cycle, and capacity tables state whether the figure already accounts for it.
  • Airflow across the indoor coil changes capacity, so a capacity row is only valid at the airflow the table names.
Where the load line and the capacity line cross

A building losing 24,000 BTU per hour at an outdoor design temperature of 5 F, heated by an air source unit rated 24,000 BTU per hour at 47 F. Published capacity falls to 13,500 at the design condition. Both lines are drawn from the same four temperatures.

The two lines cross near 20 F, so above that outdoor temperature the heat pump carries the whole load on its own. At the 5 F design temperature the building needs 24,000 BTU per hour and the unit produces 13,500, leaving 10,500 BTU per hour for supplemental heat. The load line reaches zero at 60 F rather than at room temperature, because internal and solar gains cover the last few degrees. Both lines are close to straight across this range, which is what makes the crossing solvable by hand rather than by simulation.01000020000300000204060Balance point 20 FOutdoor air temperature (F)Heat rate (BTU per hour)
  • Building heat loss
  • Heat pump capacity
  • The two lines cross near 20 F, so above that outdoor temperature the heat pump carries the whole load on its own.
  • At the 5 F design temperature the building needs 24,000 BTU per hour and the unit produces 13,500, leaving 10,500 BTU per hour for supplemental heat.
  • The load line reaches zero at 60 F rather than at room temperature, because internal and solar gains cover the last few degrees.
  • Both lines are close to straight across this range, which is what makes the crossing solvable by hand rather than by simulation.

The two lines you need before you can find a crossing

A balance point is the intersection of two relationships, and neither is the one a badge or a nameplate gives you. The first is how much heat the building loses as it gets colder outside. The second is how much heat the equipment can produce as it gets colder outside. Both change with outdoor temperature, and they change in opposite directions, which is the whole reason a crossing exists.

Building heat loss rises as the outdoor temperature falls. Heat pump capacity falls at the same time, because the outdoor coil has less temperature difference to work with and the refrigerant mass flow drops. Plotted against the same horizontal axis, one line climbs to the left and the other descends to the left. Where they meet, the equipment exactly satisfies the building with nothing left over.

Building the load line from two points

The load line is a straight line, and two points fix it. The first is the design condition: the calculated heat loss at the outdoor design temperature for the site. That figure comes from a room-by-room heat loss calculation, not from floor area. The second point is the temperature at which the heating load reaches zero.

That second point is the one people put in the wrong place. Heating load does not reach zero when the outdoor temperature reaches the indoor setpoint. It reaches zero a few degrees below it, because people, lighting, appliances, and sun already contribute heat. A building held at 70 F may stop needing heat around 60 F. Placing the zero-load point at 70 F instead tilts the whole line and moves the crossing.

In the worked example, the design loss is 24,000 BTU per hour at 5 F and the load reaches zero at 60 F. That is a fall of 24,000 BTU per hour across 55 degrees, so the building loses about 436 BTU per hour for every degree the outdoor temperature drops. Any point on the line follows from that slope.

Reading capacity at temperature rather than nominal capacity

The second line has to come from the manufacturer's expanded performance data, which lists heating capacity against outdoor temperature, indoor conditions, and airflow. A nominal two-ton rating is a cooling figure measured at one condition, and it says close to nothing about output at 5 F. Reading the table row for the actual airflow is what makes the line real.

Two details in that table decide whether the line is honest. The first is whether the stated capacity is an integrated figure that already accounts for time spent in defrost, or a steady-state figure that does not. The second is whether the row was taken at maximum compressor speed. A variable-speed unit can hold a high maximum for short periods and settle lower against a steady call, so a design drawn only from the maximum row overstates delivered heat.

In the example the published capacity falls from 24,000 BTU per hour at 47 F to 17,000 at 17 F and 13,500 at the 5 F design condition. Between the tabulated temperatures the curve is close enough to straight that linear interpolation is sound, which is what lets the crossing be solved rather than estimated from a drawing.

Working the crossing by hand

Set the two expressions equal to each other and solve for temperature. The load at any outdoor temperature is 436 multiplied by the difference between 60 and that temperature. Capacity rises by 233 BTU per hour for each degree between 17 F and 47 F, starting from 17,000 at the lower end. Equating the two gives an outdoor temperature of about 19.6 F, and both lines read close to 17,600 BTU per hour there.

Round that to a balance point of 20 F and the design statement becomes concrete. Above 20 F the heat pump meets the load unaided. Below it the equipment falls short by a gap that widens every degree, reaching 10,500 BTU per hour at the 5 F design condition. That gap, not the balance point itself, is what sizes the supplemental heat.

The same arithmetic works in metric with no change of method. A loss of 7.0 kW at minus 15 C with the load reaching zero at 15.5 C gives a slope near 230 watts per kelvin, and the crossing lands close to minus 7 C. Only the units move.

What the number changes about the rest of the design

A balance point is an input to three later decisions rather than a result to file. It sets the supplemental heat capacity, because the shortfall at design condition is the amount another heat source has to cover. It sets the control strategy, because the outdoor temperature at which backup is allowed to run should relate to the crossing rather than to a default in a thermostat menu. It sets the energy estimate, because hours spent below the crossing are the hours the expensive heat source runs.

Moving the balance point lower means buying more compressor capacity, which costs money at purchase and can hurt part-load behaviour in the shoulder seasons if the unit cannot turn down far enough. Moving it higher means a smaller unit and more resistance heat in the coldest weeks. Building America guidance frames this as a sizing strategy choice rather than a single correct answer, and the right answer depends on the local hours below the crossing and on the price of each fuel.

Where the calculation goes wrong

Four errors account for the results that do not survive a winter. Putting the zero-load point at room temperature steepens the load line and pushes the balance point colder than the building will deliver. Taking the nominal tonnage as the capacity line ignores the whole reason the calculation exists. Using cooling-driven equipment selection in a heating-dominated climate produces a unit whose capacity line was never checked against the load line at all.

The fourth is subtler. A load calculation carrying a safety margin on top of an already conservative heat loss inflates the design load, which raises the load line, which drives the crossing warmer and calls for more backup than the building needs. Margins compound, and the balance point is where the compounding becomes visible.

What moves when the balance point is set warmer or colder
Design choiceEffect at design conditionEffect in shoulder season
Warmer balance pointLarger shortfall, so more supplemental capacity has to be installed and more hours are served by itSmaller compressor runs closer to its efficient range at mild loads
Colder balance pointSmaller shortfall, less backup energy in the coldest hoursLarger compressor may cycle if its minimum output exceeds a mild load
Zero-load point set too highLoad line steepens and design load is overstatedCrossing reported colder than the building actually achieves
Capacity read at maximum speed onlyCapacity line overstated, so shortfall is understatedDelivered heat falls below the drawing during steady calls

Questions people ask about this

Is the balance point the same as the switchover temperature?

No. The balance point is a calculated property of one building paired with one machine, found where capacity meets load. A switchover or lockout temperature is a setting entered into a control, and manufacturers publish different defaults for it. A sound design uses the calculated balance point to choose the setting rather than accepting whatever the control arrives with.

Can a heat pump be sized so there is no balance point at all?

It can, if capacity at the outdoor design temperature exceeds the design heat loss. The crossing then falls below any temperature the site reaches, and no supplemental heat is needed for capacity reasons. The cost is a compressor selected well above the cooling load, which may not turn down far enough to hold a mild load without cycling.

Why does the load line stop at 60 F instead of 70 F?

Because heat entering the building from people, lighting, appliances, and sunlight covers the last few degrees of the gap. The temperature at which those gains match the fabric and ventilation loss is the zero-load point, and it sits below the indoor setpoint. Its exact value depends on the building, which is why a load calculation reports it rather than assuming it.

Does the calculation change for a ground source heat pump?

The method is identical, but the capacity line is far flatter. A ground loop delivers entering water temperature that moves across a season rather than across a day, so capacity does not collapse during a cold snap the way an air source machine's does. The crossing can fall below the design temperature, which is why ground source designs carry less supplemental heat.

Evidence record

Source verification pending

government guidance, standards body publication · editorial review

This page is awaiting source verification against the documentation in its evidence record: Pacific Northwest National Laboratory, Building America Solution Center, CIBSE Journal and Air Conditioning Contractors of America technical literature. Its documentation class and intended scope are shown here while that check is pending.

Documentation class
government guidance, standards body publication
Scope of the definition
Confirm against the exact model manual