engineering

Cleanroom temperature and humidity control: dehumidification, reheat, and dew point design

How to control cleanroom humidity: why to control supply dew point instead of room RH, the dew point each RH target needs, chilled water limits, desiccants, and reheat.

Editorial reviewBy Mukarram Haroon
Direct answer

What this means

Control cleanroom humidity through the dew point of the supply air, not the room's relative humidity. Relative humidity moves with every change in room temperature, while dew point measures the moisture actually present. A makeup air unit dries outdoor air to a dew point low enough to absorb the room's moisture release, a dry recirculation coil removes sensible heat, and reheat is added only where dried air would overcool the room. At 68°F, holding 40 percent relative humidity with six gowned people and 500 cfm of makeup air needs a supply dew point near 37°F, colder than 42°F chilled water can produce, which is where a desiccant wheel or a low-temperature coil takes over.

Equipment and model context

  • Cleanrooms with a makeup air unit handling outdoor air and moisture and a recirculation path handling sensible heat
  • Occupancy, makeup airflow, and room conditions in the example are stated assumptions; psychrometric values are at sea-level pressure

This explains temperature and humidity control strategy for cleanrooms and calculates the supply dew point a room target needs. The product, the process, or a regulation such as USP 797 sets the target itself, and the local outdoor design condition sets how hard the makeup air unit works.

What this covers

  • Why relative humidity makes a poor control variable and dew point makes a good one.
  • The supply dew point each room humidity target needs at 68°F, from 35 to 60 percent.
  • Where chilled water coils stop and desiccant or low-temperature coils are needed.
  • When reheat is needed, how much it costs, and how temperature and humidity loops avoid fighting.

What changes the result

  • The room relative humidity target and the room temperature it is paired with.
  • Occupant moisture, set by headcount, activity, and gowning.
  • Makeup airflow, which is both the moisture carrier and the drying capacity.
  • Chilled water temperature, which limits how low a coil's leaving dew point can go.

Why relative humidity is the wrong variable to control

Relative humidity is the moisture in the air divided by the most it could hold at its current temperature, so it changes whenever temperature does. Near 68°F, a room that warms by 1°F loses about 1.5 percentage points of relative humidity with no change in the moisture present. A control loop following room relative humidity sees every temperature swing as a humidity change and responds to it.

Dew point, or humidity ratio in grains of moisture per pound of dry air, measures the moisture itself and does not move with temperature. Controlling the makeup air to a dew point setpoint, and the room to a temperature setpoint, gives two loops that each have one job. The room relative humidity then follows from the two and is monitored, not controlled.

Where cleanroom temperature and humidity targets come from

For sterile compounding, USP 797 caps the room at 20°C (68°F) and 60 percent relative humidity. The ASHRAE contamination guideline for data centers keeps relative humidity below 60 percent so settled dust does not absorb enough water to become conductive. Beyond those, the product sets the target: a hygroscopic powder, an adhesive with a cure window, or a process sensitive to static each brings its own band.

Write the target as a temperature and a dew point with a tolerance for each, and state whether it applies at rest or in operation. ISO 14644-3 includes temperature and humidity tests for the finished room, and a target without a tolerance gives the certifier nothing to test against.

Split the job: makeup air for moisture, recirculation for heat

A cleanroom's moisture arrives in two ways: from outdoor air brought in for pressurization and exhaust makeup, and from the people working inside. Both can be handled at the makeup air unit, because it treats all the outdoor air and can deliver it drier than the room to absorb occupant moisture as well.

The recirculation path then only removes sensible heat. Its coil should run dry, with its surface kept above the room dew point, or it removes moisture unpredictably and competes with the makeup air unit's control. That calls for warmer chilled water for the recirculation coil than for the makeup air coil, or a separate loop, and the cleanroom heat load calculation shows the resulting split of duties for one room.

Calculating the supply dew point a target needs

Take a room at 68°F with six gowned people at light bench work. The ASHRAE Handbook, Fundamentals occupant table gives 475 BTU per hour of latent heat per person at that activity, so the room releases 2,850 BTU per hour of moisture. The makeup air unit supplies 500 cfm.

At 68°F and 40 percent relative humidity the room holds about 40.6 grains of moisture per pound of dry air. To absorb 2,850 BTU per hour, the makeup air must arrive drier by 2,850 ÷ (0.68 × 500) = 8.4 grains, at 32.2 grains per pound, which is a dew point of about 37°F. The factor 0.68 converts cfm and grains to BTU per hour for standard air, and reading a psychrometric chart shows the same state points graphically.

At 50 percent the room holds 50.9 grains, the supply needs 42.5, and the dew point is about 44°F. At 60 percent the supply dew point is about 50°F. The chart plots every target from 35 to 60 percent, and each step of 5 points in room humidity moves the required supply dew point by about 3 to 4°F.

When chilled water cannot get there

A cooling coil can only bring air toward its coolant temperature, never below it, and air leaves a real coil some degrees warmer than the water entering it. With chilled water supplied at 42°F, a leaving dew point of 37°F is out of reach whatever the coil depth, and 44°F is marginal. The apparatus dew point calculation shows how coil depth and face velocity set how close to the coolant the leaving air gets.

Below that line there are two routes. A low-temperature coil on glycol or direct expansion can reach dew points in the 30s °F, with defrost to manage where coil surfaces fall below freezing. A desiccant wheel adsorbs moisture from the air and releases it into a separate regeneration air stream heated for the purpose, reaching low dew points without freezing, and a precooling coil ahead of it removes part of the moisture at lower cost so a smaller wheel does the rest.

The desiccant route adds heat to the process air, since adsorption releases heat, so a sensible cooling coil follows the wheel. Its energy trade is regeneration heat against the refrigeration a sub-freezing coil would have needed, and waste heat from a chiller condenser or a boiler can supply part of the regeneration.

Reheat: when it is needed and what it costs

Reheat is needed when air dried to the required dew point would arrive colder than the room can accept. Cooling 500 cfm to 38°F to reach a 37°F dew point and warming it to 55°F before supply takes 1.08 × 500 × 17 = 9,180 BTU per hour of heat, spent only to undo cooling the plant has just paid for.

Much of that can be avoided. In a room where the recirculation air still needs cooling, cold dry makeup air mixed into the recirculation path offsets part of that cooling instead of being reheated. Reheat then becomes a part-load tool for nights and light process loads, when the cold makeup air alone would overcool the room. Where reheat is needed, heat recovered from a chiller condenser or a heat pump costs far less than new heat from electric resistance or a boiler.

Keeping temperature stable at high airflow

At high air change rates the supply air sits only a few degrees below the room. The USP 797 worked example on the USP 797 HVAC requirements page ends with supply just 6.6°F below a 68°F buffer room, so a 1°F swing in supply temperature is a large share of the whole cooling effect. Control the recirculation coil on supply air temperature with the room sensor resetting its setpoint, rather than driving the valve straight from the room sensor.

Keep the temperature and dew point loops from fighting. A deadband between cooling and reheat, a dew point loop that acts only on the makeup air unit, and a written sequence of operations stating which loop has priority at each condition prevent simultaneous heating and cooling that neither loop intended.

Humidifying in dry weather

In cold, dry weather outdoor air arrives with too little moisture, and rooms with a lower humidity limit need it added back. Steam is the cleanroom-compatible method, since it adds no minerals or droplets when made from treated water, and clean steam generated from purified water is the option where the air reaches exposed product.

Inject steam into the makeup air unit or supply duct far enough upstream of any filter, coil, or elbow for it to be absorbed completely, because wetted surfaces downstream of a humidifier grow microbes and wet HEPA media loses strength. Control humidification from the same dew point setpoint as dehumidification, with a deadband between the two.

Supply dew point needed for each room humidity target at 68°F

For a room at 68°F with six people releasing 2,850 BTU per hour of moisture and 500 cfm of makeup air, the makeup air dew point needed to hold each relative humidity target, beside the room's own dew point at that target.

At a 60 percent target the makeup air needs a dew point of about 50°F, which a coil on standard chilled water can deliver. At 45 percent the supply dew point falls to about 41°F, and at 40 percent to about 37°F, below the temperature of a 42°F chilled water supply, so no coil on that water can reach it. The gap between the two lines is the drying the makeup air must do to absorb occupant moisture, about 6°F of dew point across the range with 500 cfm; halving the makeup airflow roughly doubles the grains of drying each cubic foot has to provide.3040506030405060Colder than a 42°F chilled water supplyUSP 797 upper limit at 68°FRoom relative humidity target (%)Dew point (°F)
  • Makeup air supply dew point needed
  • Room dew point at the target
  • At a 60 percent target the makeup air needs a dew point of about 50°F, which a coil on standard chilled water can deliver.
  • At 45 percent the supply dew point falls to about 41°F, and at 40 percent to about 37°F, below the temperature of a 42°F chilled water supply, so no coil on that water can reach it.
  • The gap between the two lines is the drying the makeup air must do to absorb occupant moisture, about 6°F of dew point across the range with 500 cfm; halving the makeup airflow roughly doubles the grains of drying each cubic foot has to provide.
Dehumidification method by the supply dew point required
Supply dew point neededMethod that can reach itWhat to watch
Above about 50°FCooling coil on standard chilled water or direct expansionReheat or mixing where the dried supply would overcool the room
About 40 to 50°FCoil on colder chilled water, or direct expansion at a low evaporator temperatureLeaving air cannot be colder than the coolant, and the gap depends on the coil
Below about 40°FDesiccant wheel after a precooling coil, or a low-temperature glycol coilRegeneration heat for the wheel, and frost on any coil surface below freezing
Humidifying in dry weatherClean steam injected into the makeup air or supply ductAbsorption distance before any filter, coil, or elbow downstream

Questions people ask about this

What humidity should a cleanroom be kept at?

There is no single figure. The product or the regulation sets it: USP 797 says compounding rooms should be at 60 percent relative humidity or below at 20°C or cooler, while an electronics or powder process may set a narrower band. State the target as a dew point with a tolerance so the controls have a stable variable to hold.

Where should cleanroom humidity sensors be located?

Control the makeup air unit from a dew point sensor in its supply, and monitor the room from a representative point in the room or its return air. A room sensor next to a supply diffuser reads the supply, and one beside a heat source reads a low relative humidity for air that has not dried at all.

Can a desiccant wheel replace the cooling coil?

A desiccant wheel removes moisture and warms the air while it does, so a cooling coil is still needed after it to remove that heat and the room's sensible load. A precooling coil ahead of the wheel takes out part of the moisture at lower cost and lets a smaller wheel reach the target.

Why does cleanroom humidity drift when the temperature changes?

Relative humidity depends on temperature, so a room at 68°F that warms by 1°F reads about 1.5 points lower with the same moisture. If the controls follow room relative humidity, a temperature swing looks like a humidity problem and the two loops start working against each other.

Evidence record

Source verification pending

standards body publication · editorial review

This page is awaiting source verification against the documentation in its evidence record: ASHRAE, United States Pharmacopeia, International Organization for Standardization, via ANSI and ASHRAE Technical Committee 9.9 technical literature. Its documentation class and intended scope are shown here while that check is pending.

Documentation class
standards body publication
Scope of the definition
Confirm against the exact model manual